Product Overview
CFP 8 Zone Repeater Panel
CFP760
- Can be used to repeat the functions of a master CFP standard or AlarmSense 2-8 zone fire panel at remote parts of site (e.g. all potential fire service entrances).
- Up to 8 repeaters per CFP master.
- Includes its own Mains power supply that requires its own standby battery supply.
- Provides the user with access to all AL1 and AL2 functions.
- Master/Repeater communication achieved using CFP761 network driver cards (one CFP761 is supplied with the Repeater, an additional CF761 card is required at the master CFP).
- Communicates over screened two-wire fire resistant cable.
- Total repeater network cable length should not exceed 1KM.
- Attractive flush or surface mountable plastic lid and enclosure - no bezel required.
| Compatibility | Compatible with C-TEC's CFP Standard and CFP AlarmSense panels. (CFP Economy panels cannot be extended with this product). |
| Mains supply | 230V 50/60Hz. |
| Internal power supply | 19V-28.5V (27V nominal). |
| Max battery size and type | 2 x 12V 2.1Ah VRLA connected in series for 72 hour standby. 2 x 12V 1.2Ah for 24 hours. |
| Max. network cable length | 1KM. |
| Product dimensions (mm) | 380 W x 235 H x D 96mm. |
| Construction & finish | Plastic lid and base; RAL7035 textured |
| IP Rating | IP30. |
| Weight | 1.75kg (without batteries) |
| Operating conditions/temperature | -5ºC to +40ºC. Max relative humidity: 95%. |
| Product dimensions: | 367 W x 235 H x 96 D mm. |
| Hole required for flush mounting: | 367 W x 220 H x 75 D mm. No bezel required. |
CFP Panels DoC
Declaration of Conformity (EMC/LVD) DOC0000002 Rev 1